The 7011A Series is a true on-line
double conversion UPS system that sizes range from 6kVA
to 12kVA. All of the 7011A Series UPS systems incorporate
IGBT’s both in the inverter and converter sections.
The information below should help you in selecting the
correct UPS system:
Voltages: 7011A Series: 6kVA - 12kVA Standard 208,240 Volt Input;Standard 120,208,240 Volt Output, systems are hardwired and the 6kVA - 12kVA
are hardwired output with optional receptacle panels.
Batteries: Each 7011A Series UPS system
comes standard with a minimum of 10 to 18 minutes of battery
runtime. Each 7011A Series UPS system offers extended
battery runtimes in matching cabinets, up to approximately
8 hours of runtime. For longer runtimes, separate non-matching
battery cabinets are offered for backup times of up to
24 hours and beyond. For these long runtime applications,
Mitsubishi strongly recommends that the standard battery
in the UPS unit be disconnected as paralleling batteries
of different A.H. capacities is generally not good practice.
Mitsubishi also recommends utilizing a dedicated battery
charger built in the non-matching battery cabinets for
longer runtimes to properly recharge the batteries within
approximately 24 hours to ensure proper system reliability
and optimum performance.
Software: Mitsubishi offers its ‘DiamondLink’
software which performs networking monitoring and controlled
shutdown of critical servers and computers. The software
is available in a CD-ROM which supports almost all operating
systems.